Reliability analysis of 20 kV electric power distribution system based on SAIFI, SAIDI, CAIDI, MAIFI, ASAI and ASUI at PT. PLN Rayon Samalanga

Muhammad Iqbal

Abstract


The reliability index of the distribution system is a measure of the system's ability to continuously supply electrical energy to loads over a specific period and under certain conditions. PT. PLN (Persero) Rayon Samalanga, as the electricity service provider in Bireun Regency, adheres to service standards in accordance with SPLN 59:1985 and the IEEE Reliability Index standard 1366-2003. This research analyzes the reliability level of PT. PLN (Persero) Rayon Samalanga's distribution network on six (6) feeders: feeder SL-1, feeder SL-2, feeder SL-3, feeder SL-4, feeder SL-5, and feeder SL-6. The reliability index calculation is based on the estimated failure rate (λ) and the estimated interruption duration (U) for each installed component. The calculation results show that the distribution lines of PT. PLN (Persero) Rayon Samalanga are categorized as reliable according to SPLN 59:1985 and the IEEE Reliability Index standard 1366-2003, with the highest reliability index on feeder SL-4 at SAIFI = 2.04 times/failure; the best SAIDI value is on feeder SL-3 with SAIDI = 2.06852 hours/year; the best CAIDI value is on feeder SL-3 with CAIDI = 0.21 times/failure; the best MAIFI value is on feeder SL-2 with MAIFI = 14.82 times/customer; the best ASAI value is on feeder SL-3 with ASAI = 0.99999684, and the best ASUI value is on feeder SL-2 with ASUI = 0.0000081

Keywords


SAIFI, SAIDI, CAIDI, MAIFI, ASAI, and ASUI, Reliability

Full Text:

PDF

References


SPLN 52-3 “Pola Pengamanan Sistem Bagian Tiga : Sistem Distribusi 6 kV dan 20 kV”. Jakarta. PT. PLN (Persero). 1983.

Jatmiko Aziz “Analisis Keandalan Sistem Distribusi Tenaga Listrik Pada Penyulang Nusantara II di PT. PLN (Persero) Rayon Kroya Menggunakan Metode Section Technique”. Tugas Akhir. Jurusan Teknik Elektro, Fakultas Teknik, Universitas Muhammadiyah Purwokerto, 2017.

Muhammad wahid Muntasyir “Studi Analisa Keandalan Sistem Distribusi 20 KV Pada PT. PLN Rayon Palur”. Tugas Akhir. Jurusan Teknik Elektro, Fakultas Teknik, Universitas Muhammadiyah Surakarta, 2018.

Aditya Teguh Prabowo, Bambang Winardi, dan Susatyo Handoko “Analisis Keandalan Sistem Distribusi 20 KV Pada Penyulang Pekalongan 8 dan 11”. Jurnal Teknik Universitas Diponegoro Semarang, Vol. 2 No. 4, 2013.

SPLN 59 “Keandalan Pada Sistem Distribusi 20 kV dan 6 kV”. Jakarta. PT. PLN (Persero). 1985.

IEEE std 1366-2003 “IEEE Guide for Electric Power Distribution Reliability Indice”. USA. 2003.

Hendro Tri Kurniawan, Bonar Sirait, dan Junaidi “Evaluasi Keandalan Sistem Jaringan Distribusi Menggunakan Indeks Saidi dan Saifi Pada PT.PLN (PERSERO) Area Pontianak”. Jurnal Teknik Universitas Tanjungpura, 2014.

Achmad Fatoni, Rony Seto Wibowo, dan Adi Soeprijanto “Analisis Keandalan Sistem Distribusi 20 KV PT. PLN Rayon Lumajang Dengan Metode FMEA ( Failure Modes and Effects Analysis)”. Jurnal Teknik ITS, Vol.5 No.2, 2016.

SPLN 73 “Komisioning Jaringan”. Jakarta. PT. PLN (Persero). 1987




DOI: https://doi.org/10.52626/joge.v3i2.42

Refbacks

  • There are currently no refbacks.


Journal Geuthee of Engineering and Energy is published by Geuthèë Institute.
St. Teknik II, Reumpet, Krueng Barona Jaya sub-district (23370), Aceh Besar District, Aceh Province, Indonesia.
http://geutheeinstitute.com/
ISSN (Online): 2964-2655
The published content of this journal is licensed under a Creative Commons Attribution 4.0 International License.
Creative Commons License